THE WORLD
OF SCAME

Italy

Parre (Bergamo)

Please, select your language

Search product


Navigator

   

SERIES DETAILS

ADVANCE-GRP[GD] Series
Switched interlocked socket outlets [ATEX IECEx II 2 GD - GAS&DUST]


 

GENERAL DESCRIPTION
PRODUCTS FOR USE IN A POTENTIALLY EXPLOSIVE ENVIRONMENT


Scame offers products suitable for installation into environments under potential risk of explosion identified as Zone 1/2 and 21/22 and that enter into the field of application for the ATEX Directive (European Directive 94/9/CE and IECEx).

 

 

REFERENCE STANDARDS



EN 60309-1
Plugs, socket outlets and couples for industrial purposes
Part 1: General requirements.

EN 60309-2
Plugs, socket outlets and couples for industrial purposes.
Part 2: Dimensional interchangeability requirements for pin and contact-tube accessories of harmonised configurations.

EN 60309-4
Plugs, socket-outlets and couplers for industrial purposes.
Part 4: Switched socket-outlets and connectors with or without interlock.

EN 60079-0
Electrical apparatus for explosive gas atmospheres.
Part 0: General requirements.

EN 60079-31
Electrical apparatus for explosive gas atmospheres.
Part 31: Equipment dust ignition protection by enclosure.

EN 60079-1
Electrical apparatus for explosive gas atmospheres
Part 1: Flameproof enclosures "d"

EN 60079-7
Electrical apparatus for explosive gas atmospheres
Part 7: Increased safety “e”

IEC 60079-0
Electrical apparatus for explosive gas atmospheres.
Part 0: General requirements.

IEC 60079-31
Electrical apparatus for explosive gas atmospheres.
Part 31: Equipment dust ignition protection by enclosure.

IEC 60079-1
Electrical apparatus for explosive gas atmospheres
Part 1: Flameproof enclosures "d"

IEC 60079-7
Electrical apparatus for explosive gas atmospheres
Part 7: Increased safety “e”


 

 

 

TECHNICAL DATA SHEET



Rated current 16A-32A-63A-125A

Rated voltage 50÷690V~

Frequency 50÷60Hz

Insulating voltage 690V~

Protection degree IP66

Operating Temperature Range (16A-32A) -50°C to +60°C

Operating Temperature Range (63A-125A) -35°C to +60°C

Maximum permissible surface temperature T80°C (DUST)

Switched socket outlets with interlock material Thermosetting (GRP)

Impact resistance 7J

Switch-disconnectors 16A-32A-63A COMMAND-EX Series

Switch-disconnectors 125A CZ0513

Colour Black RAL9005

ATEX Code II 2GD

Ex Protection type Ex d e IIC T4, T5, T6 Gb Ex tb IIIC T80°C Db IP66

CE certificate - Certificate ATEX INERIS 15ATEX0017X

CE certificate - Certificate IECEx IECEx INE 15.0033X

Classe température et milieu (GAS) T4, T5, T6


 

 

 

BEHAVIOUR WITH CHEMICAL AND ATMOSPHERIC AGENTS



Saline solution Resistant

Acids Concentrated Limited resistance
Diluted Resistant

Bases Concentrated Limited resistance
Diluted Resistant

Solvents Hexane Resistant
Benzol Resistant
Acetone Resistant
Alcohol Resistant

Mineral oil Resistant

UV rays Resistant


 

 

Rev.16.1024      

 

Share
 
 
 
Search
Text:
Code:
Description:
 
 
Utility
Discover how to find in thousands configurations, the Combination unit for you.
Identifies the products compatible with Scame material.
 
 
Advertising
 

 
 
 
 

Search - Language [] - Site Map - Contact - Privacy - Legal Notice
©2005-2017 - SCAME PARRE S.p.A. - P.IVA IT 00137900163 - Active users: 665